News

ABB Says Weak One-Time Passwords and Hidden Factory Logins Can Take Over Relion Relays

ABB's November 27 advisory says Relion protection relays can be taken over through a weak one-time password and leftover factory accounts. It had no reports of exploitation.

ABB warned that Relion protection relays, the boxes that trip a substation when something goes wrong, can be taken over through a weak one-time password and leftover factory accounts.

Advisory 2NGA002995, dated November 27, covers CVE-2026-4641 and CVE-2026-4642. The first is a weak OTP used for password recovery. Someone with physical access and enough knowledge of the system can forge the secret and get administrative privileges. On REX640, that path can also be remote if the X0/HMI port is plugged into the station network, which ABB's own documentation says not to do. ABB scored the local case 7.4 and that remote case 8.1.

The second hole is factory accounts baked into the code. They are disabled after manufacturing, then left in the binary. A user who already has ENGINEER or ADMINISTRATOR rights, and a network path to the relay, can use them to run code. ABB scored that 6.6. A successful attack can affect functional safety. Independent researcher Ruben Santamarta reported the bugs. ABB said it had no reports of exploitation when it published.

Patches exist for the current REX615 and REX640 lines: SW 6.2.1 (PCL3) for REX615, and SW 6.2.1 (PCL7) for REX640. Older 610, 611, 615, 620, and SMU615 units get physical and network hygiene instead of a firmware fix. Keep the front port off the station LAN, and watch for security log 1730, an admin password reset to factory default. Industrial controllers keep showing leftover factory doors. Danfoss fridge boxes had their own unauthenticated path this month.

Some offers on this page may be paid placements or contain affiliate links.